Combined Transformer of Amorphous Alloy Iron Core
Combined Transformer of Amorphous Alloy Iron Core
Supplier Info
[China Supplier]
Contact Person : Ms. Ju Maggie
Tel : 86-570-4016599
Fax : 86-570-4016599
Product Detail
1.The transformer's no-load loss is only 20~25% of the ZGS9. 2.The size is about 1/3 of that in China with the same capacity.

The ZGSBH15 (16) series transformers are in accordance with the national standard JB/T10217-2000 Padmounted Transformer, JB/T10318–2002 Technical Parameters and Requirements of Oil-immersed Amorphous Alloy Core Distribution Transformer, and the enterprise standard Q/321284JCA39-2003 Padmounted Transformer.

The ZGSBH15 (16) series transformers are made of amorphous alloy core. The no-load loss of products is greatly reduced. It is only 20~25% percent of the ZGS9 series. Therefore, products are suitable for areas without sufficient electrical energy and with great fluctuation of electric loading. The products are energy-saving.

Structural features

The core is made of amorphous alloy. The no-load loss of products is greatly reduced. It is only 20~25% of the ZGS9 series.The transformer chamber, high-voltage chamber, and low-voltage chamber are in optimized combination. They are pre-formed in the factory. Therefore, the structure of the product is simplified. The size is about 1/3 of that in China with the same capacity. The transformer is suitable for residence communities, commercial entertainment center, and street lamps in cities. It will be useful for saving the land resource.Products totally sealed and insulated without any exposed electrified component and are safe and reliable.Cases are of corrosion protection design. Special spray painting treatment is used. Products are suitable for using under severe environment.

Insulation level of product

Voltage class

kV

Effective value of the highest voltage of the equipment

kV

Effective value of rated short-duration power frequency withstand voltage

kV/min

Full-wave peak value of rated lightning impulse withstand voltage

kV

≤1

≤1.1

5

/

6

7.2

25

75

10

12

35

95

20

24

50

120

Performance characteristic parameters

Capacity

kVA

Voltage combination

Connection symbol

No-load loss

W

No-load current

 

%

Load loss

75°C   W

Short-circuit impedance

 

75°C  %

High voltage

KV

Tapping scope

Low voltage

KV

50

6

6.3

10

20

±2*2.5%

0.4

Dyn11

43/38

1.30/0.9

870

4

80

60/46

1.1/0.7

1250

100

75/58

1.0/0.7

1500

160

100/78

0.7/0.5

2200

200

120/90

0.7/0.5

2600

250

140/110

0.7/0.5

3050

315

170/130

0.5/0.4

3650

400

200/160

0.5/0.4

4300

500

240/190

0.5/0.4

5150

630

320/230

0.3

6200

4.5

800

380/280

0.3

7500

Note:

1. Figures before the oblique line are for 15 model and after the oblique line are for 16 model.

2. The outside dimension of the product with high voltage of 20kv shall be decided by both the buyer and seller.

3. The dimension in the table is for reference. The installation and design shall be subject to the outside dimension stated in the contract of our company.