Welcome to ECOL - Join Free - Sign In
Partial Discharge Testing Device Set
Partial Discharge Testing Device Set
Supplier Info
[China Supplier]
Contact Person : Ms. Liu Abby
Tel : 86-29-82258667,82258674,82258672
Fax : 86-29-82242382
Product Detail
A: CNJF2008 Partial Discharge Testing Device B: CNJF2008-1 Calibration pulse generator C: 2 pcs of input units.

CNJF2008 Partial Discharge Testing Device

1. Requested Service Condition:

1.1. Ambient temperature: 0 20°C±2°C

1.2. Relative humidity: ≤80%

1.3. Power supply: 220V±22V,50HZ

1.4. Should not be subject to severe vibration and mechanical shock

1.5. The air should not contain enough dust and impurities to erode device. 

1.6. Should not be subject from strong electromagnetic interference.

1.7. Good ventilation

1.8. Grounding requirements: Ground resistance  1Ω

2. Capacity range of testing sample: 6PF--250μF

3. The sensitivity can be detected (please check below Table 1)

Input unit serial no.

Adjustment capacity

Unit 

Sensitivity (micro-micro coulomb)

(asymmetric circuit)

1

6-25-100

Micro micro farad

0.02

2

25-100-400

Micro micro farad

0.04

3

100-400-1500

Micro micro farad

0.06

4

400-1500-6000

Micro micro farad

0.1

5

1500-6000-25000

Micro micro farad

0.2

6

0.006-0.025-0.1

micro farad

0.3

7

0.025-0.1-0.4

micro farad

0.5

8

0.1-0.4-1.5

micro farad

1

9

0.4-1.5-6.0

micro farad

1.5

10

1.5-6.0-25

micro farad

2.5

11

6.0-25-60

micro farad

5

12

25-60-250

micro farad

10

7R

Resistance 

0.5

4. Magnifier Band

4.1. Low terminal:  10KHZ , 20KHZ, or 40KHZ, it’s up for you to choice.

4.2. High terminal: 80KHZ, 200KHZ, or 300KHZ, it’s up for you to choice.

5. Magnifier adjustment:

There are six position for coarse adjustment, the gain between gears is 20±1db; Fine adjustment range 20db.

6. Time window:

6.1 The showing color of time screen window is yellow. 

6.2. Window width: adjustable range: 15° 150°

6.3. Window position: each window can rotate 0°  170°

6.4. there are 2 time windows. These 2 time windows can be used at the same time or separately to be used.

7. Electricity discharge meter

Ø It is a digit head of form. 

Ø 0 – 100.0 can be shown by  3½LED digit. 

Ø The Error ±5% (counted as full graduation)

8. Ellipse time base

Ø Frequency is 50HZ, the frequency can be choused arbitrarily.

Ø The color of oval display is blue.

Ø The rotation of oval: each 30° as one gear position, it can rotates 180°.

Ø Showing mode: ellipse -- straight line

Ø The base oval can be adjusted to normal size at high frequency when input voltage (13 275V), its ingestion power 1V.

9. Testing voltage meter

Ø Measurement range: 100KV (extensible)

Ø Showing: 3½ digital voltage meter indication

Ø Accuracy: better than ±5% (counted as full graduation)

10. Inner and outer nil-mark function

11. Volume : 450*450*215 (width * depth *height ) mm3

12. Weight : about 12kg

Partial Discharge Testing Device Set

Ads by Google

Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.