Ads by Google
Electrical Features | Standard | Unit | IEC/EN 60898-1 |
Rated Current In | A | 1 2 3 4 6 10 16 20 25 32 40 50 63 | |
Poles |
| 1P 2P 3P 4P | |
Rated Voltage | V | 240/415 | |
Insulation Voltage | V | 500 | |
Rated Breaking Capacity | A | 3000 | |
Rated impulse withstand voltage | V | 6000 | |
Dielectric test voltage | KV | 2 | |
Pollution Degree |
| 2 | |
Thermo-magnetic release Charccteristic |
| BCD | |
Rated frequency | Hz | 50/60Hz | |
Mechanical Features | Electrical Life |
| 4000 |
Mechanical Life |
| 8000 | |
Contact Position Indicator | Yes | ||
Protection Degree | 1P 20 | ||
Reference Temperature for Setting of Thermo Element | °C | 30 | |
Ambient temperature | °C | -5- +40 | |
Storage Temperature | °C | -25- +70 |