Ads by Google
Compared with normal oil immersed power transformer has no oil storage box, and adopts the corrugations on the oil tank as its heat-radiation parts. The oil tank is made by fine cold-rolled steel on an exclusive production-line. The corrugations can expand or contract according to the change of oil volume. Thus the inner space of transformer can be isolated from the air, which can reduce the aging speed of oil and prevent the insulation materials from damping. Oil-immersed transformer possesses a reliable operation, and is free from maintenance. For more information, special requirement, please contact us.
Rated power(kVA) | Voltage combination and tapping range(kV) | Connectionsymbol | No-loadCurrent(%) | Loss(W) | Impedance (%) | Gross weight(kg) | ||
HV | LV | No-load | load | |||||
10 | 6.0±5% Or 11±5% | 0.4 | Yyn0 Or Dyn11 | 3.8 | 55 | 310 | 4.0 | 245 |
20 | 3.0 | 80 | 475 | 290 | ||||
30 | 2.1 | 100 | 600 | 330 | ||||
50 | 2.0 | 130 | 870 | 410 | ||||
63 | 1.9 | 150 | 1040 | 480 | ||||
80 | 1.8 | 180 | 1250 | 560 | ||||
100 | 1.6 | 200 | 1500 | 690 | ||||
125 | 1.5 | 240 | 1800 | 880 | ||||
160 | 1.4 | 290 | 2200 | 940 | ||||
200 | 1.3 | 340 | 2600 | 1160 | ||||
250 | 1.2 | 400 | 3050 | 1320 | ||||
315 | 1.1 | 480 | 3650 | 1550 | ||||
400 | 1.0 | 570 | 4300 | 1730 | ||||
500 | 1.0 | 680 | 5150 | 2190 | ||||
630 | 0.9 | 840 | 6200 | 4.5 | 2460 | |||
800 | 0.8 | 980 | 7500 | 2750 | ||||
1000 | 0.7 | 1150 | 10300 | 3220 | ||||
1250 | 0.6 | 1360 | 12000 | 3800 | ||||
1600 | 0.6 | 1640 | 14500 | 4500 | ||||
2000 | 0.6 | 2100 | 17100 | 5545 | ||||
2500 | 0.5 | 2500 | 23200 | 5.0 | 6220 |