DYT 400 Serial smart temperature transmitter
DYT 400 Serial smart temperature transmitter can divide into three specifications
DYT400-1H Serial smart temperature transmitter
DYT400-2H Serial smart temperature transmitter
DYT400-3H Serial smart temperature transmitter
DYT400-1H is thermal resistance input type, PC machine programmable
DYT400-2H is thermal resistance, thermocouple input PC machine
Programmable.
DYT400-3H is thermal resistance, thermocouple input, HART or PROFIBUS-PA protocol
\
Feature:
DYT400-1H series intelligent temperature transmitter converted signal from Pt100 into 2 wire DC 4~20mA output which correspond to the temperature and no relate to overload, can be programmable by standard PC machine, 3 wire thermal resistance configuration mode, upper and low limit alarm can be programmed, The precision is 0.1%, with sensor open loop detection function, and enhance capability of anti electromagnetic interference.
DYT400-2H series intelligent temperature transmitter converted signal from thermal resistance, thermocouple into 2 wire DC 4~20mA which corresponding to a temperature and unrelated to overload. can be programmable /configuration by standard PC machine, ,3 wire thermal resistance configuration mode, upper and lower limit alarm can be programmed, Input / output electric isolation, precision 0.1% ( typical), the stability of0.1%/ (typical), independent of the alarm circuit, excellent capability of anti electromagnetic interference. With independent parallel alarm circuit, continuous self diagnosis and self calibration.
Technical data:
Input: thermal resistance Cu50Pt1002line,3line or 4 line K, N, E thermocouple, J, T, R, S, B etc.
CJC compensation : in situ <0.5 °C<0.2°Cremote
RTD measurement current: 0.2mA, continued
The cable impedance : T>600 °Cmaximum 10 ohm/wire
3/4) T<600maximum30 ohm/wire
Protection: +/-35Vac
Suppress: 50/60hz
Resolution: 16
Repeatability: <0.05 °C
Output;
Signal interval:4-20mA,2;20-4mA,2 wire
Resolution: 12
Accuracy: <0.2%
Response time: Pt1001.0sec; T/C1.6sec
Power range: 8-35Vac
Damping:0-15sec
Filters pulse: 3Vms
Upper / lower calibration limit: 23mA/3.5mA
Environmental:
Operating temperature: -40°C - 85 °C
Storage temperature: -55°C - 90
Humidity: <98%RH
Protection grade: shell IP55
DYT 400 smart temperature transmitter