pt100 temperature sensor controller XMT7100 1.Sensor can be RTD or thermocouple 2.PID output pt100 temperature sensor controller

1. Product Highlights

Thermocouple: T, R, J, B, S, K, E, Wre3-Wre25.

RTD: Pt100, Cu50.

1 Relay output, 1 SSR controlled output.

Time proportional PID controlled output to either Relay or SSR

Three built-in algorithms that fit most control objects and various applications.

Temperature can be set to display in either Fahrenheit or Celsius degrees.

2. Specifications

Supply voltage: 18-265V AC or DC

Power consumption: < 2 Watts.

Sampling speed: 4/sec.

SSR activated voltage: open circuit: 10V; short circuit: 40mA.

Accuracy: 0.2% of full scale.

LED Display: Red, 0.28 inch

Out of range indication: “EEEE”.

Ambient temperature requirements: 0 to 50 C (32 to 122 F)

Humidity requirement: < 85% RH.

Relay Contact: 220VAC, 3A.

Controller dimensions: 48 x 24 x 75 (mm).

Opening for installation: 44 x 20 (mm)

3. Auto-Tuning

By simply pressing a single button, the built-in artificial intelligent is activated to automatically

calculate and set parameters ( P, I, d, SF, Bb, Ot ) that fit the condition to be controlled.

Figure 3

a) How to start and stop the auto-tuning process:

i. To activate auto-tuning, press and hold (>) until “AT” indicator blinks, which indicates autotuning

is in progress. When auto-tuning finishes, the “AT” indicator light turns off. Now newly

calculated PID parameters are stored in memory and will be used by the controller.

ii. To EXIT during the auto-tuning process, press and hold (>) until “AT” indicator turns off.

The previously entered PID parameters values are used by the controller.

4. Connection Terminals (back view).

5. Device Application Example

Figure 8

User wants to control internal temperature (T) of boiler by measuring the surface temperature of the

boiler. A surface mounted, Type K thermocouple is chosen. Boiler surface is to be maintained at 225

deg F. System power supply is AC120V. Installation opening is 44 x 20(mm). A solid state relay

(SSR) with a rating of 25A will be used to control the heating element.

a) Choose XMT-7100 with input from a Type T thermocouple.

b) See Figure 8 for connection diagram.

c) Parameter settings:

(Inty) = t

(Outy) = 2

(CAty) = 0

(PSb) = 0

(Rd) = 1

(CorF) = 1

(filt) = 0

(auto-tuning will be used to set PID parameters)

(SV) = 225 deg F

(AH1) = 325 deg F

(AL1) = 325 deg F

Power up the controller and press (>) to activate auto-tuning. When “AT” stops blinking, new PID

parameters are generated for the system. The controller is in normal operation mode.