Introduction SPS-48/600-2900 Power System adopts modularized design, consists of Smart Power I 48/2900, an intelligent DKD41 controller, AC and DC distribution unit. Up to twelve rectifier modules can be equipped in the system cabinet to reach 600A system capacity maximum. SPS 48/600-2900 cabinet power supply system is designed to meet higher power efficiency and versatile technical requirement. Compact structure, fully integrated functions of rectifier and system make SPS 48/600 2900 typical applications are providing 48V standby power for central data center and wireless transmission center. Intelligent system management features include battery temperature compensation, fast charge, battery current limit, automatic equalize charging and automatic battery condition monitoring. With a compact power and distribution design, the system provides a maximum flexibility with a variety of possibilities.
Applications Wireless, Wire-line communication Broadband and network access Data center access 3G center base station Transmission center station
Main Features High efficiency, energy-saving, green DC power. Digitalized Primary and secondary controls could realize excellent monitoring and regulation. Ethernet interface built-in. High reliability design. Advanced battery management capacity Battery asymmetry control. Excellent EMC performance. Lower interference and excellent susceptibility give module better reliability. Global approvals: CE marked, UL recognized and TUV certified.
Technical Specifications |
|
AC Input Voltage | 1/2/3P+N+PE, Nominal 220/230/380/400/415VAC |
Frequency | 45 ~ 65Hz; |
Power Factor | ≥ 0.99 |
Efficiency | ≥ 94%, Rated; 95% maximum. |
Voltage wave distortion | < 5% |
DC Output Voltage | -48V(nominal); |
VoltageRange | -42V ~ -57.6V; |
Current | 1500Aultimate capacity |
Peak-peak noise | ≤ 200mV; |
Psophometric noise | ≤ 2.0mV |
Audible noise | ≤ 55dBDC |
Rectifier | Smart Power I 48/2900 |
Controller Model: | DKD41 |
Local operation | Menu driven software via keypads and LCD or PC |
Remote operation | Modem/On-board web server/SNMP |
Alarms Relays | 8 relays |
Digital inputs | 9 options (for external equipment and battery) |
Operating temp. | -5 to +55° C |
Storage temp. | -40 to +70° |
Relative humidity | < 90%, no condensing |
Atmospheric pressure | 70Kpa~106KPa |