12V 12AH storage battery for power backup supply
Decriptions:LEOCH LPX series ups storage battery with high current Features:1. Silver-coated copper terminals (T1, T2 terminal), brass insert terminals and lead terminals improve the electric conductivity2. Thin plate technology, special grid design, unique paste formula and plate curing process optimize high rate performance3. High quality AGM separators with less electrical resistance improve high current discharging properties4. ABS material: increase the strength of battery container (Flame-retardant ABS is optional)Typical Applications:1. UPS (High rate) High2. power backup supply3. Emergency power supply4. Starting system5. Power tools6. Emergency lighting7. Electric starting
specifications:
Battery Model | LPX storage battery 12V 12AH | |
Nomial Capacity(15min Rate) | 49.8 Watts at 1.67V/cell | |
Dimension | Length | 151± 1mm (5.95 inches) |
Width | 98 ±1mm (3.86 inches) | |
Container Height | 95 ±1mm (3.74 inches) | |
Total Height (with Terminal) | 101± 1mm (3.98 inches) | |
Approx Weight | Approx 4.2 kg (9.26lbs) | |
Terminal | T1 / T2 | |
Container Material | ABS | |
Rated Capacity | 12.6 AH/1.26A (10hr ,1.80V/cell,250C/770F) 12.0 AH/1.50A (8hr,1.80V/cell,250C/770F) 10.5 AH/2.10A (5hr,1.75V/cell,250C/770F) 9.45 AH/3.15A (3hr,1.75V/cell,250C/770F) 8.77 AH/8.77A (1hr,1.60V/cell,250C/770F) | |
Max. Discharge Current | 180A (5s) | |
Internal Resistance | Approx 14 mΩ | |
Operating Temp.Range | Discharge : -15~500C (5 ~1220F) Charge : 0~400C (32 ~1040F ) Storage : -15~400C (5~1040F) | |
Nominal Operating Temp. Range | 25±30C (77±50F ) | |
Cycle Use | Initial Charging Current less than 2.1A.Voltage 14.4V~15.0V at 250 C(770 F)Temp. Coefficient -30mV/0C | |
Standby Use | No limit on Initial Charging Current Voltage 13.5V~13.8V at 250 C(770 F)Temp. Coefficient -20mV/0C | |
Capacity affected by Temperature | 40 0C (104 0 F) 103% 25 0C ( 77 0F ) 100% 0 0C ( 32 0F ) 86% | |
Self Discharge | Leoch LPX series batteries may be stored for up to 6 months at 250 C(770F) and then a freshening charge is required. For higher temperatures the time interval will be shorter. |
12V 12AH storage battery for power backup supply