High voltage electric pin type insulator
1) PIN tpye insulators2) Main material:porcelain
3) standard: ANSI,IEC,ISO9001,KEMA etc.
4) Item NO.: 56-1, 56-2, 56-3, 56-4, 56-5 series
Remark
Sample available
MAIN DIMENSIONS AND STANDARD PARTICULARS AS FOLLOWING TABLE:
Class ANSI | 56-1 | 56-2 | 56-3 | 56-4 | 56-5 | |||
Fig. NO | 1 | 1 | 2 | 2 | 3 | |||
Main Dimensions mm | H | 146 | 165 | 191 | 241 | 318 | ||
h | 50.8 | 50.8 | 50.8 | 50.8 | 63.5 | |||
D | 191 | 228 | 267 | 305 | 343 | |||
d | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | |||
R1 | 19 | 19 | 19 | 19 | 19 | |||
R2 | 14 | 14 | 14 | 14 | 14 | |||
Nominal Voltage/KV | 23 | 23 | 35 | 46 | 69 | |||
Creepage Distance/mm | 330 | 430 | 533 | 685 | 865 | |||
Minimum Flashover Voltage | Power-Frequency | Dry/KV | 95 | 110 | 125 | 140 | 175 | |
Wet/KV | 60 | 70 | 80 | 95 | 125 | |||
50% Impulse | Positive/KV | 150 | 175 | 200 | 225 | 270 | ||
Negative/KV | 190 | 225 | 265 | 310 | 340 | |||
Radio-Influence-Voltage Date | Test Voltage to Ground/KV | 15 | 22 | 30 | 30 | 44 | ||
Maximum RIV at 1000kHz/KV | 100 | 100 | 200 | 200 | 200 | |||
Low Frequency Puncture Voltage Average/KV | 130 | 145 | 165 | 186 | 225 | |||
Dry Arcing Distance(mm) | 178 | 210 | 241.3 | 285 | 356 | |||
Cantilever Failing Load(id) | 1134 | 1360 | 1360 | 1360 | 1360 | |||
Weight/kg | 3.7 | 5.3 | 7 | 10.8 | 13.5 |
we sincerely hope our hardworking, our products can service more and more clients from all over the world, so, if you are interested in our products, please don't hesitate to contact us. Fzbonle also accepts ODM and OEM orders!
Looking forward to your reply! we will arrange everything for you.
High voltage electric pin type insulator