Welcome to ECOL - Join Free - Sign In
GW4-40.5/72.5/126/145/252 Disconnector
GW4-40.5/72.5/126/145/252 Disconnector
Supplier Info
[China Supplier]
Contact Person : Mr. Yi Xu
Tel : 86-411-39803333
Fax : 86-411-39803301
Product Detail
Disconnector GW4-40.5/72.5/126/145/252 the series of GW4 disconnector are double-column horizontal rotating structures

Disconnector GW4-40.5/72.5/126/145/252

Main feature

the silver layer of contact is thick and rigid, so it has reliable electric and mechanical performance.

the motor mechanism isCJ5B mechanism, the manual mechanism is CSA or CS17 or CS19 mechanism.

Ambient:

Ambient Air Temperature:      -40~+40°C

Ice Coating thickness:            10mm

Wind-pressure:                       700(34m/S) Pa

Seismic level:                          8 degree

Altitude:                                   1000 or 2000 m

Technical parameters

ItemUnitGW4-40.5GW4-72.5GW4-126GW4-145GW4-252 
Rated VoltagekV40.572.5126145252
Rated CurrentA3150

630/1250/2000/3150

20003150
Rated Short Time Withstand Current(3s)kA4025/31.5/40/504050
Rated Peak Withstand CurrentkA10063/80/100/125100125
Rated Short Time Power Frequency Withstand VoltageTo EarthkV70140230275460
Across Open Contacts80160265315530
Rated Lightning Impulse Withstand VoltageTo Earth kV1703255506501050
Across Open Contacts1953756307501200
Creepagemm/kV25 or 31
Isolating Distance After Main Contact Openmm53095012501550

>=2450

 Isolation distance after earthing blade openmm  560520 910 1180 

>=1800 

 Bending force of porcelain insulator4000 6000
 Torsion foce of porcelain insulatorN.m  2000     