Ads by Google
18/30(36)kv Three core copper conductors XLPE insulated to IEC 60502-2 steel tape armored cables. Cable Construction: 1. Copper conductor 2. Semiconductive conductor screen 3. XLPE insulation 4. Semiconductive Insualtion screen. 5. Copper tape screen 6. Fillers 7. Tape binder 8. Bedding 9. Galvanized steel tape armour 8. Outer sheath.
Conductor diameter(MAX) | KV | 18/30(36)KV | ||||||||
Nominal area of conductor | mm 2 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 |
Conductor diameter(MAX) | mm | 8.4 | 9.9 | 11.6 | 13 | 14.5 | 16.1 | 18.4 | 20.6 | 23.7 |
Weight of conductor(Approx) | Kg/Km | 1281 | 1845 | 2558 | 3219 | 3954 | 4966 | 6526 | 8187 | 10428 |
Insulation thickness(Nominal) | mm | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.6 | 2.8 | 3 |
Separation sheath thickness | mm | 1.3 | 1.4 | 1.4 | 1.5 | 1.6 | 1.6 | 1.7 | 1.8 | 2 |
Steel tape thickness(Nominal) | mm | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.8 |
Outersheath thickness(Nominal) | mm | 2.4 | 2.5 | 2.7 | 2.8 | 2.9 | 3 | 3.2 | 3.4 | 3.7 |
Approximate overall diameter | mm | 47.0 | 50.5 | 54.5 | 58.0 | 61.5 | 65.5 | 71.5 | 77.5 | 86.0 |
Approximate cable weight | Kg/Km | 3650 | 4500 | 5590 | 6510 | 7690 | 9000 | 11210 | 14010 | 18330 |
Minimum bending radius of cable(during installation) | mm | 560 | 604 | 652 | 692 | 736 | 781 | 853 | 928 | 1028 |
Maximum DC resistance of conductor at 20 degree | ohm/Km | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 | 0.0991 | 0.0754 | 0.0601 | 0.047 |
Approximate AC resistance of conductor at 90 degree | ohm/Km | 0.493 | 0.343 | 0.247 | 0.196 | 0.159 | 0.128 | 0.099 | 0.080 | 0.064 |
Approximate reactance at 50Hertz | ohm/Km | 0.11 | 0.10 | 0.10 | 0.09 | 0.09 | 0.09 | 0.09 | 0.08 | 0.08 |
Approximate impedance at 50Hertz | ohm/Km | 0.5 | 0.36 | 0.26 | 0.22 | 0.18 | 0.15 | 0.13 | 0.12 | 0.1 |
Approximate capacitance of cable | uf/Km | 0.34 | 0.38 | 0.43 | 0.47 | 0.51 | 0.56 | 0.61 | 0.63 | 0.65 |
Approx. charging current per phase at Uo=12KV and f=50HZ | mA/m | 0.38 | 0.43 | 0.49 | 0.53 | 0.58 | 0.63 | 0.69 | 0.71 | 0.74 |
Sustained current ratings | ||||||||||
1.Laid direct,ground temp.30 degree &g=1.2 degree m/W,depth of laying=0.8m,laid in trefoil touching | A | 187 | 227 | 267 | 303 | 338 | 383 | 436 | 481 | 534 |
2.Drawn into ducts,ground temp.30 degree &g=1.2 degree m/W,depth of laying=0.8m,laid singly | A | 161 | 191 | 227 | 258 | 294 | 329 | 378 | 418 | 472 |
3.Laid in air in trefoil touching,Ambient temp.35 degree | A | 203 | 248 | 304 | 345 | 396 | 451 | 524 | 598 | 681 |
One second short circuit current rating of conductor | kA | 7.15 | 10.01 | 13.60 | 17.20 | 21.50 | 26.50 | 34.30 | 42.90 | 57.20 |
33KV 3 core CU/XLPE/STA/PVC