Paper Wrapped Conductor | |||||
Product instruction | |||||
Single paper wrapped conductor uses bare copper flat wire or paper wrapped flat wire as core of conductor,and insulating paper wrapped.high mechanical ability and Anti-short circuit ability,widely used in large and medium-sized transformer winding coil | |||||
Type of insulating paper | |||||
telephone paper,cable paper,high density interturn paper,dannisong paper,TYVEK etc. | |||||
Dimension range of conductor | |||||
a:0.8~15b:2.0~23 | |||||
Prouduct Technical Parameters | |||||
Dimensional deviation | |||||
Conductor dimensional deviation | |||||
Standard size(mm) | National standard deviation(±) | Inner quality standard(bare conductor) | Inner quality standard(paper wrapped bare conductor) | ||
Side a | a≤3.15 | 0.03 | -0.02~0 | -0.02~0 | |
3.15<a≤6.30 | 0.05 | -0.03~0 | -0.03~-0.01 | ||
6.30<a≤7.10 | 0.07 | -0.05~0 | -0.05~-0.02 | ||
7.10<a≤9.10 | 0.08 | -0.06~0 | -0.06~-0.02 | ||
Side b | b≤3.15 | 0.03 | -0.02~0 | 0~+0.02 | |
3.15<a≤6.30 | 0.05 | -0.03~0 | +0.01~+0.03 | ||
6.30<a≤12.50 | 0.07 | -0.05~0 | +0.02~+0.05 | ||
12.50<a≤15.00 | 0.09 | -0.06~0 | +0.02~+0.06 | ||
Corner radius | |||||
Corner radius comparison | |||||
Range of side a | Angle R | Deviation(±) | |||
1.00<a≤1.60 | 0.5 | 25% | |||
1.60<a≤2.24 | 0.65 | ||||
2.24<a≤3.55 | 0.8 | ||||
3.55<a≤6.00 | 1 | ||||
6.00<a≤7.10 | 1.2 | ||||
Thickness of insulating paper | |||||
Thickness of insulating paper | Deviation(±) | ||||
greater than> | Less than or equal to≤ | ||||
- | 0.5 | -10 | |||
0 | |||||
0.5 | 1.25 | -7.5 | |||
0 | |||||
1.25 | - | -5 | |||
0 | |||||
Resistivity | |||||
Less than or equal to≤0.017241Ω.M M2/ M | |||||
Half hard copper index | |||||
Half hard copper performance index | |||||
Model | Yield strength | Minimum elongation | Maximum resistivity | ||
C1 | 100~180 | 20 | 1/58 | ||
C2 | 180~200 | 20 | 1/57.5 | ||
200~220 | 15 | 1/57.5 | |||
C3 | 220~260 | 15 | 1/57 | ||
Soft state copper index | |||||
0.8<a≤2.00 | ≥30% | ||||
2.00<a≤4.00 | ≥34% | ||||
4.00<a≤6.3 | ≥36% | ||||
Monolayer insulating paper breakdown voltage | |||||
0.4~0.8KV | |||||
Springback Angle | |||||
Less than or equal to≤5º | |||||
Executive standard | |||||
GB/T 7673.1-2008GB/T 7673.3-2008 |