Test Sets Composed of:
High Accuracy CT site Calibrating Test Sets are composed of seven items as below:
-Instrument Transformer Tester, Model ITC-C,
-Standard reference CT, Model HL-62CS
-Current load box ,model FY-96, two piece, 1A one piece, 5A one piece
-Current Injection, model SL-7
-Test console,model TC-20
-Current cable set
Software is simple, used for upload data to computer.
Description:
The test set used for CT site calibration at power frequency state. The tested CT accuracy can reach up to 0.02S.
The test method apply for IEC60185
Product Features:
-Adopting differential measurement principle for ITC-C;
-ITC-C can be tested for CT or PT;
-Automatic sampling at test point
-Automatic identification of the polarity fault and the ratio mistake.
Technical Specifications:
Instrument Transformer Tester, Model ITC-C
-Input: Power Frequency: 50Hz±0.5Hz, Power Voltage: 220V±5V
-Range
² Ratio Error (%): 0.0001 ~ 200.0 resolution 0.0001
² Angle measure (°): 0.001 ~ 700.0, resolution 0.001
² Resistance measure: (ohm): 0.0001 ~ 20.0 resolution 0.0001
² Lead-time (ms): 0.0001 ~ 20.0 resolution 0.0001
-Basic Error
² Ratio error: triange X=±(X×2%+Y×2%)±Dx (Class 1 option)
² Angle error(º): triangle Y = (Y*2%+X*2%*34.48) ± Dy (Class 1 option)
² “X”,“Y”——Values Displayed
² “Dx, Dy”——Quantified Error Dx=2, Dy=5
-Working Range
² Current:(1%-149%)In (In =5A)
(5%-149%)In (In =1A)
² Voltage:(5%-149%)Un (Un =100V,150V,100V/)
(5%-200%)Un (Un =100V/3)
-Working Load
² Current: TO to TX<0.12 ohm cosΦ=1.0
² Voltage: a to x<0.25VA (100V)
-Power Consumption
-Less than 15VA (without micro-printer), Less than 25VA (with micro-printer)
-Harmonic control >40db
-Polarity Check/ Indication
Standard reference CT, Model HL-62CS
-Rated load : 5VA,1VA PF=1.0
-Be allowed to wok long time at rated current ,the wire must be through the core if the current is over 150A.
-Standard current ratio:
² Primary:5,7.5,10,15,20,25,30,40,50,60,75,80,100,120,150,160,200,250,300,315,400,
² 500,600,630,750,800,1000,1200,1250,1500,160,2000,2500,3000,3150,4000,5000A
² Secondary:5,1A
-Accuracy class:0.02S
-Temperature: 5°C ~ 40°C,Humidity: <80%
Test control, model TC20 :
-Capacity: 20kVA+500VA (tiny adjusting)
-Input voltage: AC 220V±10% 50Hz±1
-Output voltage: AC 0~250 V
-Input current: 100A
-Ambient Temperature: -20°C to 50°C
-Meter accuracy class:1.0
-Timing range:0-999S
Primary Current Injector, model SL-7:
-Rated capacity:20KVA
-Input voltage : 0~250V
-Output current: 0~5000A
-Surface temperature rise: <75 °C
-No-load consumption;<2%
-Continuous working at full-load: 5min
-Intermittent working time: 15min
Current Load Box, model FY-96
-Power source frequency: 50Hz
-Rated capacity :80VA or 60VA
-Secondary current:5A or 1A
-Measurement range:5%-120%
-Power factor:0.8,1
-Accuracy class: ±3%
-Test voltage:2KV
-Temperature: 5°C ~ 40°C
-Humidity: <80%(25°C)
-Altitude :< 2500m
High Accuracy Current Transformer Calibrating Tester/Testing