Welcome to ECOL - Join Free - Sign In
PMAC720 LCD 220V Modbus Power Meter
PMAC720 LCD 220V Modbus Power Meter
Supplier Info
[China Supplier]
Contact Person : Mr. Zhou Jackey
Tel : 86-756-3629673,3629699
Fax : 86-756-3629600,3629700 Address: No.15, Keji 6 Road, Chuangxin Haian, Tangjia Hi-tech Zone, Zhuhai, Guangdong Zip: 519085 Country/Region: China (Mainland) Province/State: Guangdong
Product Detail
220V LCD Power Meter, 5A rated input metering volt, amp, kW, kvar, kWh, kvarh, Hz Harmonic, RS485, DI+DO, Modbus/ Profibus,

The PMAC720 Multifunction Power Analyser is suit for up to 220kV system.

The compact device is designed for monitoring and displaying electric parameters include voltage, current, active power, reactive power,  power factor, frequency, active energy and reactive energy.

Additional, PMAC720 is user-configurable enable users to add extendable DI/DO modules. The auxiliary functions (SOE, TOU. harmonic analysis, dual-RS485 com) are so powerful enough to satisfy different applications.

Feature:

1. Suit for LV/ HV voltage system

2. Compact design with all real-time measurement

3. Consist of basic unit and optional modules

4. 10 years back-up of integrated energy data

5. Large LCD, high brightness, auto-scrolling

6. High accuracy, V or I is 0.2%, kWh is class 1

7. CT and PT programmable

8. Pluggable terminals, easy to install

9. Panel size: 96 x 96mm

10. Password protect

Basic Function:

Provide one RS485 communication, measures and display real-time parameters:

1. Voltage—Ua, Ub, Uc, Uab, Ubc,  Uca,

2. Current—Ia, Ib, Ic, In

3. Active power – Pa, Pb, Pc, ∑P

4. Reactive power –Qa, Qb, Qc, ∑Q

5. Power factor—PFa, PFb, PFc, ∑PF

6. Frequency

7. Active energy—kWh 

8. Reactive energy– kvarh

Optional Modules:

1. 4 status input (dry contact) + 4 relay output

2. 8 status input (dry contact) + 2 relay output

3. 4 status input (wet contact) + 4 relay output

4. 8 status input (wet contact) + 2 pulse output

5. 2 pulse output + 2 analog output

 Optional Function: 

1. Up to 31st harmonic analysis, K factor, THD

2. SOE (event log)

3. TOU (multi-tariff)

4. One 4~20mA analog input

5. One 4~20mA analog output

Accuracy:

ParameterAccuracyResolutionMeasuring range
Voltage0.2%0.01

direct 520V ph-ph

PT primary; 0~999999V

Current0.2%0.0010~49999A
Power0.5%0.10~100MW/ Mvar
Power factor0.5%0.001-1.000~+1.000
Frequency0.010.0145~65Hz
Active energy1.0%0.10~99,999,999.9kWh
Reactive energy2.0%0.10~99,999,999.9 kvarh
Individual harmonic1.0%0.0010~100%
Un-balance1.0%0.0010~100%

PMAC720 LCD 220V Modbus Power Meter