Overview
The W5100DL Series Alternating current data acquisition module is used in High voltage electric and Low voltage ac circuit fields. It can collect the data about three-phase voltage, active power and reactive power.
High performance industrial product;
Standard Modbus RTU protocol;
RS232 or RS485 port ;
Functions :
1. Electric parameters include: three-phase ac voltage data, current data, active power, reactive power, power factor, zero sequence current, zero sequence voltage;
2. 3-channel switch control signal output;
3. 6-channel swith signal input, also can be used as pulses signal input;
4. 4-channel DC input, can be connect with many kinds of transmitter;
5. 2-channel RS232/RS485 communication port, support Modbus RTU protocol;
6. Apply to all kinds of bad electromagnetic interference environment;
7. Support redundancy communication is that 2 Modbus commuication channels are established at same time;
Technology parameters
1. Alternating Current Input:
Measurement object: three-phase voltage, line voltage and three-phase current;
Measurement parameters: three-phase voltage V1, V2, V3; three-phase current I1, I2, I3; active power P1, P2, P3; reactive power Q1, Q2, Q3; gross active power P; gross reactive power Q; Power factor; Frequency; zero-sequence current 3IO; zero-sequence voltage 3UO;
Voltage Input: 400V/ 660V/ 1140V;
Current Input: 0~5A;
Sample rate: Each cycle waves sampling 16 points;
Update time: 40MS
Accuracy: 0.5%
2. DC analog signal input:
Channel number: 4-channel
Signal input: 0~5V, 0~20mA, 4~20mA;
Conversion time : 5uS
Accuracy: 0.5%
3. Pluse signal input ( switch signal input and pluse signal input share port ):
Channel number: 6-channel;
Signal Input protection: Light coupling isolation;
Rated Input: DC 12~48V;
Scanning mode: Interrupt scanning;
Counting Frequency: 10KHz;
Minimum Pulse Width: 0.2ms;
4. Switch Signal Input
Channel number: 6-channel;
Signal Input protection: Light coupling isolation;
Rated Input: DC 12~48V
5. Switch Signal Onput
Channel number: 3-channel;
Contact rating: 250V/3A AC
6. Communication ports:
Channel number: 2-channel;
Mode: RS232 or RS485
Protocol: Modbus RTU
7. Voltage Input: DC12~24V
Power consumption: <5W
Temperature range: -20°C~70°C
Alternating Current Data Acquisition Module