Basic Parameter | Primary current(A) | Secondary current(mA) | Resistance Rb(Ω) | Maximum currant(A) | Class | Remark | ||||||||
10 | 5 | 20 | 60 | 0.1 | DC42.4A | |||||||||
Current error and phase error limited | Class | Current error±(%) | Phase error( )
| |||||||||||
0.01In | ≥0.05In | 0.01In | 0.05In | 0.2In | 1In | 2In | 3In | Imax | ||||||
0.1 | 0.2 | 0.1 | 15 | 8 | 5 | 5 | 5 | 5 | 5 | |||||
|
|
|
|
|
|
|
|
|
| |||||
Note,between the current 0.2In~Imax,taking the average δe between the maximum and minimum phase error. δi=δi-δe.(δI: phase error,δI: phase displacement when the working current at i time,δe:average phase displacement) | ||||||||||||||
Half-sinusoid Test | At 42.4A, the energy measurement error is less than 3%. | |||||||||||||
Working Atmosphere | Limiting ambient temperature -40°C~+70°C,Relative humidity (RH) ≤98(25°C),Altitude ≤3000m | |||||||||||||
Main Electric performance | The withstand voltage between the primary and secondary windings is no less than 3kV and insulation resistance is no less than 1GΩ |