multi-loops power analyzer YD2080 1.Measure 3U,12I etc. 2.LCD display 3.RS485 port 4.Matched CT

Multi-loops Power Anaylzer:

Intelligent Power Analyzer YD2080 is a powerful, safe, reliable measurement and control devices, can be widely used in power systems, environmental monitoring such as low-voltage distribution automation. Two models of transformer input optional: CT20(5A/10 mA, 50A/10mA)and CT18(50A/10mA). It achieves the following functions:

Measuring voltage and each circuit current;

Measuring forward/reverse active power and forward/reverse reactive power

Measuring power factor

Measuring frequency

Measuring phase-phase angle and forward/reverse phase voltage

Counting current active power energy of each circuit

With phase-sequence detection & one way DI control

With 3DI

Technical Index

External

Host dimension:96 mm×96 mm×61mm

Trepanning dimension: 92 mm×92 mm

Display type:LCD

Measurement: applied to 3 phase 4 wire(balance/unbalance),3 phase 3wire(balance/unbalance)

Voltage(RMS)

Measurement range: 30~600V(line voltage  20~400V(phase voltage)

PT ratio:1~10

Input power consumption:≤0.25VA(220V)  ≤0.60VA(600V)

Continuous overload: 800V

Current(RMS)/Circuit

Measurement range:0~10mA

CT ratio:1~10

Input power consumption:0.2VA

Continuous overload: 2 times

Power/Circuit

Single phase power:0~3000W/var/VA(50A  transformer: 30000W/var/VA)

Total power: 0~9000W/var/VA(50A  transformer: 90000W/var/VA)

 Frequency

 Measurement range: -1~1

 Auxiliary power supply

 DC18~90V

Power consumption≤5VA 

Accuracy

Current & Voltage: 0.5%

Power & Power factor: 1%

Frequency: 45~60Hz±0.1Hz

Active energy: 1%

Insulation capacity

Among voltage/current/power supply/enclosure: 2.0kV/min·2mA

Between output/power supply: 2.0kV/min·2mA

 Working condition

 Working temperature: -10°C~50°C

Storage temperature: -25°C~75°C

Relative humidity: 20~95%RH without condensation

Electromagnetic compatibility

Surge: power supply: 4kV  I/O:2kV

 Electrical fast transient/burst: power supply: 4kV,2.5kHz  I/O:2kV, 5kHz

Electrostatic discharge: contact discharge:6kV  air-gap discharge: 8kV

Radio frequency electromagnetic field: 10V/m moderate-intensity electromagnetic radiation(eg, less than 1m from the mobile radio)

 Communication

Port: RS485

Address: 1~247

Baud rate: 1200/2400/4800/9600/19200/38400

Parity bit: N/E/O

Data bit: 8bit

Stop bit:1bit

Communication protocol: Modbus

  DI & DO function

3DI input

Mark

Index content

 Note

DI1

Power-cut

When power-on normally, DI1 is in close status, and when power-cut, and the second loops is power-on, DI1 closed, and the indicator blinking. Simultaneously, the time of power-on in the second loop on the LCD is timing.

DI2

SPD fault

When it errors, DI2 closed and the indicator blinking

DI3

Tripping for air-switching

When it tripping, DI3 closed, and the indicator blinking

1DO output

Phase-sequence fault: When the phase sequence is normal (UA, UB, UC), the positive sequence voltage = average phase voltage, negative sequence voltage is 0, DO in a disconnected state; when the phase sequence fault (UA, UC, UB), the positive sequence voltage is 0, negative sequence voltage = average phase voltage, DO in the closed state, the indicator lights.