Product Detail
1> High effeciency modular system 2> Hot plug 3> 19''2U for each module

TN280 Inverter module

1>         N+1 redundant configuration with active current sharing technology supporting up to 8 modules to be connected in parallel

2>       Pure Sine Wave, with THD<3%

3>       TN280 is available in 2KVA, 3KVA and 4KVA rated with size 2Ux6U

4>       Hot plug

5>     Active current sharing technology

6>        Can be configured into a 3-phase system

7>       DC-AC isolation improving system security

8>        Excellent Dynamic responses

9>       Max efficiency up to 85-90%

10>       Complete protection

11>       EMI/EMC

TN280D  Monitor module

Module size : 19’’2U.

With LCD and LED, it allows the user to monitor the system status in real time and read all parameters including voltage, current, frequency and capacity etc. It can also record the alarm history. Meantime, it offers communication interface (RS232 or RS485) for PC software monitoring and relay dry contact.

Static transfer switch (STS)

It increased the system availability and security by automatic transfer between the inverter and AC main. By setting up the priority of operation mode, user can change the systems status of “on line mode” or “standby mode”

The on line mode will use the output power provide by the inverter and when the inverter fails, the line will switch to AC main. The transfer time is less than 4ms. In standby mode, the system power is always connected to AC main and will switch to inverter when AC main fails. The transfer time is less than 4ms preventing power interruption. 

 

1>       Integrated design with monitor and static transfer switch

2>         Working mode selectable (AC priority or DC priority )

3>         RS485 or RS232 communication port

4>         Relay dry contact

5>        Quick transfer time, typically less than 1/4 cycle

TN280 Inverter module

Electrical

 

 

 

Model

TN281,TN282,TN283

DC Input

Norminal Voltage

48VDC, 110VDC, 220VDC

Operating range

.-18% - +25%

AC Output

Output power

1KVA,2KVA, 3KVA

Wave form

Pure sine wave

Power factor

0.8

Nominal output

110/120VAC, 220/230/240VAC

Voltage variation

Max ± 2%

Output frequency

50/60Hz ± 0.1%

THD

<3% liner load

<5% non-liner load

Crest factor

.3:1

Efficiency

Max 88%

Overload

150% 1min

125% 10mins

Dynamic response time

< 20ms

 

 

TN280 monitor & STS module

TN280A

10KVA

TN280B

20KVA

TN280C

30KVA

MONITOR

LCD

4x16 character

LED

working status

Alarm

LED, audible

Communication Interface

RS485 or RS232

4 x Dry contact

 

 

STS

 

Input

Voltage range

:-25% - +20%

Frequency range

: ±10%

Output

Work mode

AC priority or inverter priority

Transfer time

less than 1/4 cycle

Rated power

Various