Can replace SWEP's E5AS and B5. Flat Plate Heat Exchanger, Brazed Plate Heat Exchanger CE, UL, TUV,ISO9001:2000
Technical parameter
Product nameHeat Exchanger
Product modelB3-12A
Unit heat exchanging area0.012m2
Maximum flowrate4m3/h
Plate material316L or 304 stainless steel
Welding material99.9% copper
Thickness of plate0.3mm
Volume per channel0.018L
maximum number of plate60
Design pressure

1.0MPa 3.0MPa

Test pressure2.0MPa 4.5MPa
Design temperature

-195 ~+220

Connections

the biggest screw thread pipe for  water: 3/4", the biggest welded pipe for liquid: 7/8"

Refrigeration Capacity1-5KW
Basic Procedures

F1-> F3 F4-> F2

Application scopeWall-mounted Heater, Heating Water Heater, Low Temperature Testing Equipment, Small-sized Refrigeration Equipment, etc.
How Heat Transfer Works

Heat transfer occurs when there is a difference in temperature between two mediums. Heat will travel from the hot source to the cold source. The rate at which the heat transfer occurs at is determined by many factors such as the heat conductivity of the two materials andthe difference in temperatures of the two mediums. Convectiuve heat transfer occurs when the materials are moving against each other.

Plate heat exchangers have significantly good heat transfer rates because they use metal plates which have high heat conductivity rates and the plates are extremely thin. The plate heat exchangers also achieve high amounts of heat transfer through convective forces with both working fluids. With large temperature differentials, great amounts of heat transfer can be achieved using a plate heat exchanger.

Corrosion

Corrosion is usually how these units will fail. Use fluids with reasonable pH levels to ensure a long lasting life. Hard water will corrode faster than regular water. (Use distilled if possible; Distilled should never corrode it) Salt water will corrode stainless steel very fast. It is recommended to clean the exchanger often if you are using corrosive fluids. Normal usage (non-corrosive fluids) should expect 10-20 years of life. Fluids containing chlorides will corrode the unit quickly.

Applications

This is an extremely popular unit for wood burning furnaces, radiant floor systems, refrigerant systems, straight vegetable oil conversions, beer chilling, air conditioning system and solar water heating systems. It will work for any application in which the desired result is for two fluids (liquid or gas) to exchange heat.

How it Works

Fluid A passes from the port on the left of the heat exchanger through every other channel created by the plates to the opposite end port on the left of the heat exchanger (looking at it the long way). Fluid B passes from the port on the right through the other channels created by the plates and comes out the other port on the right side. The fluids are essentially touching each other through the plates and heat is transferred from the hot fluid to the cold fluid. (but the fluids do not mix)