S type H.V.HRC current-limiting fuses is insert installation.The striker parallels to the fuseelement made of pure silver.It is sealed in the fuse tube filled with chemically treated high-purity quartz sand.The fuse tube is made from beat resistance,high duty ceramic or expoxy glass when fault circuit happens,the fuse link melts,the high-resistant metal wire paralleling to fuse links melts immediately at the appearance of the arc,and the striker jumps out to push the chained equipment contact,signaling the melting automatically cuttng the circuit.The striker has spring type and powder type.Spring type striker use energy released by spring to push the strker;Power type striker use high pressure caused by the lighting powder to push the striker,S type H.V.HRC current-limiting fuses has many merits as high current-limintingh ablilty,high breaking capacity,quick and punctual in action,reliable in performance.
Selection of proper fuse links for transformer protection
transformer capacity KVA | transformer primary voltage | |||
7.2kv | 10kv | 20kv | 30kv | |
50 | SDL.J-7.2KV/8A | SDL.J-12KV/3.15A | SDM.J-24KV/3.15A | SDQ.J-40.5KV/3.15A |
100 | SDL.J-7.2KV/16A | SDL.J-12KV/6.3A | SDM.J-24KV/6.3A | SDQ.J-40.5KV/6.3A |
125 | SDL.J-7.2KV/20A | SDL.J-12KV/6.3A | SDM.J-24KV/6.3A | SDQ.J-40.5KV/6.3A |
160 | SDL.J-7.2KV/25A | SDL.J-12KV/8A | SDM.J-24KV/8A | SDQ.J-40.5KV/6.3A |
200 | SDL.J-7.2KV/31.5A | SDL.J-12KV/10A | SDM.J-24KV/10A | SDQ.J-40.5KV/8A |
250 | SDL.J-7.2KV/40A | SDL.J-12KV/12A | SDM.J-24KV/12A | SDQ.J-40.5KV/10A |
300/315 | SDL.J-7.2KV/50A | SDL.J-12KV/16A | SDM.J-24KV/16A | SDQ.J-40.5KV/10A |
400 | SDL.J-7.2KV/63A | SDL.J-12KV/20A | SDM.J-24KV/20A | SDQ.J-40.5KV/16A |
500 | SDL.J-7.2KV/80A | SDL.J-12KV/25A | SDM.J-24KV/25A | SDQ.J-40.5KV/16A |
630 | SDL.J-7.2KV/100A | SDL.J-12KV/31.5A | SDM.J-24KV/31.5A | SDQ.J-40.5KV/20A |
750/800 | SDL.J-7.2KV/125A | SDL.J-12KV/40A | SDM.J-24KV/40A | SDQ.J-40.5KV/25A |
1000 | SDL.J-7.2KV/160A | SDL.J-12KV/50A | SDM.J-24KV/50A | SDQ.J-40.5KV/31.5A |
1250 | SDL.J-12KV/63A | SDM.J-24KV/63A | SDQ.J-40.5KV/40A | |
1600 | SDL.J-12KV/80A | SDM.J-24KV/80A | SDQ.J-40.5KV/50A | |
2000 | SDL.J-12KV/100A | SDM.J-24KV/100A | SDQ.J-40.5KV/63A |
High Voltage Current Limited Fuse for Transformer Protection