Electronic flow switch (Thermal differential type)
Principle Based on the principle of thermal theory, there are two resistances in the closed probe . One resistance was heated and regarded as detected resistance , the other one was heated and regarded as standard resistance . When the medium is flowing ,the heat on the heated resistance will be taken away and the resistances’ value will be changed . The differential resistances value is the basis of determining the flow velocity .
Feature1,No movable parts . 2, Maintenance free. 3,Easy installation. 4,Suitable for variable diameter demand . 5, Switching value can be adjusted continuously. 6,Extremely low pressure loss . 7,Compact structure . 8, LED indicator display flow trend and switch state .
Application Suitable for the gas and liquid measurement . Can used for pneumatic and hydraulic systems, flow monitoring for recycled water, cutting fluid and lubricating oil , the protection of pump’s run idle .
Technical data set range :1…150cm/s(water), 3…300cm/s(oil),20…2000cm/s(air)Output: PNP, NPN, Relay , NO+NC (SPDT)Power supply :24V±20%DCSwitching Current : Max.400mA(PNP or NPN type ), Max.4A( Relay type )Unload current: Max.80mAFlow indicator : LED (6)Set type :potentiometer setProof Pressure range: 100barTemperature gradient: 4°C/s Response time :1--13s,standard is 2sInitialization time : 8sElectrical protection: reversed-phase , short circuit ,overload protectionProtection class: IP67Medium temperature :-20--80°CEnvironment temperature :-20--80°CStorage temperature :-20--100°CConnection :M12 connector /2m cable (option)Material: Probe is stainless steel . Housing is PBT .Weight :0.4kg