Conventional Fire Alarm Control Panel ODH1000
Conventional Fire Alarm Control Panel ODH1000
Supplier Info
[China Supplier]
Contact Person : Mr. Zhang Barry
Tel : 86-755-26787499
Fax : 86-755-26787499
Product Detail
The professional ODH1000 is a 4/8/16 -zone, Class B conventional fire alarm control panel, meet the latest UL864&EN54 standard.

Key words: Fire alarm Control Panel,conventional fire alarm control panel,  fire alarm panel, fire alarm, FACP, fire alarm system, fire-fighting, fire panel, fire alarm controller, fire alarm control unit

Features

1) 4/8/16 Style B (Class B) Initiating Device Circuits (IDCs).

    - All zones accept two-wire smoke detectors and any normally-open contact devices.

    - Zones 1 4/8/16 configured as general alarm zones.

2) All circuits are power-limited and supervised, meeting the latest ULC requirements using fuseless technology.

3) Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).

4) NACs may be programmed:

    - Silenceable

    - Non-Silenceable

    - Auto-Silence (program 5 to 20 minutes)

5) 1.25 amps of NAC power

6) 3.0 amps of total system power

7) Alarm, Trouble and Supervisory, Form-C relays standard.

8) 24-volt operation

9) Resettable four-wire smoke detector power @ 500 mA

10)  Non-resettable power @ 500 mA

11) Integral battery charger capable of charging up to 18 AH batteries (batteries over 4 AH require use of the external battery backbox, or ULC listed equivalent).

12) One-man walk-test programmable for silent or audible test

13) Disable/Enable control per IDC

14) Reverse polarity protection

15) Control buttons:

      - Mode

      - Test

      - ACK (Acknowledge) Alarm Silence

      - Reset

16) Meet UL864, EN-54 standard.

17) LED indicators:

      - AC Power (green & yellow LED)

      - Fire Alarm (red LED)

      - Trouble (yellow LED)

      - Supervisory (yellow LED)

      - Signal Silence (yellow LED)

      - Battery Power (green & yellow LED)

      - Zone Disable (yellow LED)

      - NAC Fault (yellow LED)

      - NAC Disable (yellow LED)

      - 4/8/16 Zone Alarm (one for each zone) (red LED)

      - 4/8/16 Zone Trouble (one for each zone) (yellow LED)

      - Earth Fault (on circuit board)

      - Battery Fault (on circuit board)

      - Charger Fault (on circuit board)

Specifications:

AC Power: AC220V±10% 50Hz, 2.0 amps, minimum 14 AWG wire (2.0 mm²) with 600-volt 

                insulation.

Battery: Sealed lead-acid batteries only, Maximum charging circuit: 27.6VDC @ 0.8 amp for

             normal flat charge, Maximum battery charger capacity: 18AH battery

             NOTE: two 4AH batteries can be housed in the cabinet. Larger batteries require a

             separate battery box.

Total 24 V system power: 3.0 amps         

Notification appliance (signal) power: 2.5 amps

Maximum current per NAC: 1.25 amps (expandable to 2.5 amps)

Auxiliary Outputs:   - Resettable four-wire smoke detector power @ 500 mA

                             - Non-resettable power @ 500 mA

                             - Integral Form-C Alarm, Trouble and Supervisory relays, rated at: 2.0

                               amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive).

NOTE: Total current for auxiliary power outputs and two NACs must not exceed 3.0 amps.

Dimensions: 320×260×80mm (length × width × depth)

Using Environment: Temperature: 10°C~+50°C  Related Humidity: ≤95% (40±2°C)

Orena Sales and Service

Shenzhen Orena Photonic Technology Co., Ltd

Orena Bldg, Zhong'an Industrial Park, Longjing Road, Nanshan District, Shenzhen, 518055, China..

Ph: 86.755.2678.7499      

Fx: 86.755.2678.1400.