LW35 High Voltage Circuit Breaker SF6
LW35 High Voltage Circuit Breaker SF6
Supplier Info
[China Supplier]
Contact Person : Mr. Yi Xu
Tel : 86-411-39803333
Fax : 86-411-39803301
Product Detail
High Voltage Circuit Breaker LW35-72.5/126/145/252 SF6 circuit breaker high voltage Simple Structure Compactness

   

High Voltage Circuit Breaker  

Main Features of High Voltage Circuit Breaker

    LW35-72.5/126/145 circuit breaker is either three-phase gang operation with a sping mechanism or single-phase operation with three spring mechanism.

    LW35-252 circuit breaker is equipped with three spring mechanisms to realize single-phase operation or three-phase electrical gang operation.

Ambient of High Voltage Circuit Breaker

                                      

LW35-72.5/126/145            LW35-252

Ambient air temperature     -40~+40°C

Wind-pressure                     ≤700 Pa

Seismic level                        ≤9 degree

Altitude                                  ≤3000              ≤2000 m

Technical Parameters of High Voltage Circuit Breaker

AMBIENT of High Voltage Circuit Breaker

   Item

Unit

LW35-72.5

LW35-126

LW35-145

LW35-252

Rated Voltage

kV

72.5

126

145

252

Rated Current

A

3150

4000

Rated Frequency

Hz

50

Rated Short Circuit Breaking Current

kA

40

50

Ambient Condition

Item

Unit

LW35-72.5

LW35-126

LW35-145

LW35-252

Ambient Temperature

°C

 -40°C~+40°C   

Wind Pressure

Pa

  ≤ 700   

Altitude

m

  ≤ 3000  

  ≤ 2000

Seismic Level

degree

  ≤ 9   

Air Pollution Level

class

II~IV

 

Main Technical Parameters

 Item

Unit

LW35-72.5

LW35-126

LW35-145

LW35-252

Rated Voltage

kV

 72.5

126

145

252

Rated Current

A

 3150  

 4000

Rated Frequency

Hz

50   

Rated Short Circuit Breaking Current

kA

 40  

50

Rated Short Time Withstand Current(3s)

kA

 40  

50

Short Line Fault Breaking Current

kA

 30/36  

45/37.5

Rated Peak Withstand Current

kA

 100  

125

Rated Out-of-phase Breaking Current

kA

 10  

 12.5

Rated Line Charging Breaking Current

A

10

31.5

50

160

Rated SF6 Gas Pressure(at 20°C)

MPa

 0.4

  0.5

 0.6

 Main Loop Resistance

µΩ

  ≤ 40

 ≤ 45 

  ≤ 60

 Operation Sequence

 O-0.3s-CO-180s-CO   

 Mechanical Endurance

Times

 10000   

  SF6 Gas Leakage Rate(per year)

%

  ≤ 1   

 Moisture Content(V/V)

Ppm

  ≤ 150   

 Creepage Distance 

Across the open contacts

MM

 2300

 3950

  ≥ 3950

 7812

To earth

MM

 2300

3950

  ≥ 3950

7812

SF6 Gas Pressure (at 20°C)

Item

Unit

LW35-72.5

LW35-126

LW35-145

LW35-252

Rated Working Pressure, PN     

MPa

0.4±0.015

0.5±0.015

0.5±0.015

0.6±0.015

Pre-filled Gas Alarming Pressure 1

MPa

0.35±0.015

0.45±0.015

0.45±0.015

0.52±0.015

 