Conversion Kit/Emergency Conversion Kit
Conversion Kit/Emergency Conversion Kit
Supplier Info
[China Supplier]
Contact Person : Mr. zhang fang
Tel : 0086-760-23838519
Fax : 0086-760-23838520
Product Detail
Conversion Kit/Emergency Conversion Kit 1auto-test 2OEM 3CE&RoHS cer 4For T5/T8 Flourescent Lamp with emergency function

Conversion Kit/Emergency Conversion Kit

Emergency Light Instruction Manual

 (ML-N06 EMERGENCY CONTROL UMIT)

 

Dear customer:

Thank you for purchase Malon series product.

For proper usage, please read this manual carefull before application.

OVERVIEW

Malon emergency light, adopted high efficiency T5/T8 fluorescent tube, specialized in low consumption, long life span and high efficiency of electrical -to-optical converting.The device, instantly alternating operatation status on power interruption, conflagration, earthquake, indicating precise emergency exit direction, is applicable to hotel, restaurant, shopping mall and tall building etc.

This series of product could be used as normal lighting in general; While the AC shutted down, the emergency lighting activates instantly no matter how the status of the switch.

Key Figure

NOMINAL VOLTAGE      AC220~230V50/60Hz

CHARGE PERIOD       ≤ 24 hours

LAMP                    T5-28W

DURATION                ≥ 90 mins

RATED LUMEN OUTPUT    T5-35W 260Lm  T5-28W 100Lm

IDEAL TEMPERATURE  -5°C ~ +45°C

BATTERY               Ni-Cd 6V 2.5A h

SPECIFICATION

Primary power indication while AC input, red LED is on; on the contrary, red LED turns off.

Discharge protection power discharge to 80% of the nominal voltage, discharge circuit would cut off autonomously to saveguard the life-span of battery.

Illuminant this series of product adopts fluorescent light for illuminate, providing high-degree brightness and energy saving.

Method of wiring:

Read the wiring diagram on the wiring concentrator of the light body for detail information.

Caution

1. For proper usage, please read this manual carefull before charging on AC.

2. The main power of the emergency light should be pluged into individual switch rather than with the same switch for general light or electrical equipment.

3. For illuminant replacement, the substitution must be with the same specification parameter. Since the device plugged into AC220V, power interruption should be primary prior to guarantee safety.

4. The device adopts evacuated Ni-HM battery pack, please charge for 24 hours before application. The initial duration might be insufficient by prolonged unocupation, please charge/discharge for 3 times thoroughly (charge for 18 hours and discharge until the battery empty), then the battery would be recovered.

5. For fuse replacement, the substitution must be with the same specification parameter (Read the nominal parameter on circuit board). Since the device plugged into AC220V, power interruption should be primary prior to guarantee safety.

6. After application, please immediately plug into AC220V and charge for 24 hours. Prolonged unoccupation might affect the battery life-span, we suggest to charge/discharge every 3 months minimum. Charge/discharge every 6 months in general application. Replace the battery while discharging period is 50% less than the nominal regulation. For detail information on battery, please contact with the manufacture.

7. On application, device must be ground connected by grounding sign.

PRODUCTION DATE:

Malon Electrical Factory

No.27 North Dong'an Road,

Haizhou District,

Guzhen Town,

ZhongShan City,

Guangdong Province,

China

Post Code:528422

Tel: (86) 0760 22314216

Fax: (86) 0756 23838520

....

Conversion Kit/Emergency Conversion Kit

Ads by Google

Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.