1>MOQ:2000M
2>Supply Abilities: 3000000M/Month
3>FOBShanghai 0.08USD/M
4> SGS ISO9001:2008
(2841-W)Specifications: 1) Thermal class: F (155°, C) 2) Loss of weight at calcination: 27% ± 2% 3) Tensile strength before curing: ≥ 1000N/cm 4) Thickness (mm): 0.30 5) Width (mm): 20, 25, 30 6) Storage time: 3-- 12 months
Properties: |
Type | 2850-W | 2841-W | 2830 | Thermal class | H | F | B | Volatile content | ≤2% | ≤4% | ≤5% | Loss of weight at calcination | 26%±2% | 26%±2% | 26%±2% | Soluble resin content | ≥90% | ≥90% | ≥90% | Tensile strength before curing | ≥2000N/cm(0.33mmT) | ≥1500N/cm(0.3mmT) | ≥500N/cm(0.17mmT) | Maximum pull while banding | 1500N/cm | 1000N/cm | 400N/cm |
|
Specification: |
Thickness (mm) | Width (mm) | Length (M/pancake) | 0.17 | 10,15,20,25,30 | 250 | 50 | 100,120 | 0.3/0.33 | 10,15,20,25,30 | 200 | 50 | 100 |
|
* Special specification and package are availabe upon request, (such as spool) |
Curing cycles: |
Temperature (°C) | 160 | 150 | 135 | 120 | 115 | Time (hour) | 5 | 6 | 8 | 16 | 24 |
|
* The above times do not include the time for the workpiece to reach the curing temperature. |
Storage stabili: |
Storage temperture °C | 10 | 15 | 20 | 30 | Time (month) | 12 | 10 | 6 | 3 |
|
Insulation Glass Fiber Banding Tape Used For Transformer